Chapter IX — BUILDING REGULATIONS›Article 1 — AMENDMENTS TO THE CALIFORNIA BUILDING STANDARDS CODE [BUILDING CODE]
Los Angeles Municipal Code § 91.2700 Basic Provisions
Los Angeles Municipal Code · 2026-10 edition · updated 2026-10-19 · Los Angeles
Cite as: Los Angeles Municipal Code § 91.2700 · Text as of 2026-10-19
(Division Amended by Ord. No. 181,758, Eff. 8/8/11.)
Section
91.2700 Basic Provisions.
SEC. 91.2700. BASIC PROVISIONS.¶
(Amended by Ord. No. 187,719, Eff. 1/23/23.)
Chapter 27 of the CBC is hereby adopted by reference, except that Los Angeles Municipal Code Subsections 91.2702.2.11.1, 91.2702.2.16.1, and 91.2702.2.19.1 are added.
91.2702.2.11.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)
91.2702.2.16.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)
91.2702.2.19.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s). (Readopted by Ord. No. 188,797, Eff. 12/31/25.)