Skip to content

Division 27

SEC. 91.2700. BASIC PROVISIONS.

Los Angeles Building Code — LAMC Chapter IX · 2026-08 edition · updated 2026-09-09 · Los Angeles

(Amended by Ord. No. 187,719, Eff. 1/23/23.)

Chapter 27 of the CBC is hereby adopted by reference, except that Los Angeles Municipal Code Subsections 91.2702.2.11.1, 91.2702.2.16.1, and 91.2702.2.19.1 are added.

91.2702.2.11.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).

91.2702.2.16.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).

91.2702.2.19.1. Fuel Supply. An on-premises fuel supply, sufficient for not less than 6-hour full-load operation of the emergency and standby power source(s), shall be provided. This fuel supply shall not be less than 8-hour when the load also includes fire pump(s).