Division II — ADMINISTRATION. PART I. – GENERAL PROVISIONS.

Chapter 2 — DEFINITIONS.

San Francisco Fire Code · edición 2022 · actualizado 2026-07-08 · San Francisco

Esta sección aún no está traducida y se muestra en inglés.

SECTION 202.

The following San Francisco Fire Code definition replaces [1] the corresponding California Fire Code definitions in Section 202:

[For SF] STANDPIPE SYSTEM, CLASSES OF. A standpipe system is a wet system of piping, valves, outlets and related equipment designed to provide water at specified pressures and installed exclusively for the fighting of fires, including the following:

Class I is a standpipe system equipped with 3-inch (76.2 mm) outlets.

Class II is a standpipe system directly connected to a water supply and equipped with 1½-inch (38.1 mm) outlets and hose.

Class III is a standpipe system directly connected to a water supply and equipped with 3-inch (76.2 mm) outlets or 3-inch (76.2 mm) and 1½-inch (38.1 mm) outlets when a 1½-inch (38.1 mm) hose is required. Hose connections for Class III systems may be made through 3-inch (76.2 mm) hose valves with easily removable 3-inch by 10-inch [1] (76.2 mm by 38.1 mm) reducers.

CODIFICATION NOTE

1. So in Ord. 248-22.

[For SF] CRITICAL AREAS. Areas that are designated for the highest level of emergency responder radio coverage including but not limited to areas such as exit stairs, exit passageways, elevators, elevator lobbies, fire protection equipment room and control valve locations, and fire command

centers.